Suggested checklist questions
CIC - Secondary containment systems: Bunds, dykes and berms
This publication on Common Inspection Criteria is intended to share knowledge about technical measures and enforcement practices related to major hazard control and implementation of the Seveso Directive. The criteria were developed by Seveso inspectors to aid in dissemination of good enforcement and risk management practices for the control of major industrial hazards in Europe and elsewhere. This particular issue provides criteria for inspecting a site’s management and maintenance of open collection systems intended for containing accidental leaks or spills from storage vessels. Note that this document is not intended as a technical standard nor as a summary or replacement of any existing standards on the matter.
DEFINITION
This CIC will focus on inspection of bunds (and similar structures) around large immobile industrial storage tanks, typically found in tank farms, but also sometimes indoors (when conditions permit), and also around indoor reactors and pressure vessels. The CIC is also generally applicable to open collection systems used for mobile indoor and outdoor containers (drums, barrels and IBCs), consisting mainly of drip trays and small scale spill containment berms.
Secondary containment is, in essence, a second line of defense for preventing, controlling or mitigating major hazard events. It is intended to stop the spread of a release when control measures associated with the primary containment system have failed. Numerous situations can arise at a hazardous site that necessitate the presence of secondary containment, in particular, poor handling during loading and unloading, overfilling, valve malfunction, and fires and earthquakes that cause primary containment to fail. Even when a proper maintenance programme is followed, various other factors, e.g., wrong procedures, a flawed risk assessment, or an external event, can create unforeseen leaks or fractures in the primary containment.
SCOPE
The secondary containment technologies addressed in this CIC are open spill collection systems designed to manage a pooling substance, that is, a hazardous substance that is a liquid, or is likely to liquefy in a fire. There are several technologies that contain liquid spills, and are used either for supplementary or full containment. A subset of these technologies consists of open spill collection systems, particularly bunds, berms, and drip trays. These particular technologies are all commonly used to prevent the spread of liquids spilled or leaked from containers of liquid substances, in particular, storage tanks, barrels, and intermediate bulk (IBC) containers. They are all more or less open basins, of varying shapes and sizes, surrounded by walls, with a few additional features that distinguish one from the other. Figure 1 shows what a typical tank storage area looks like when surrounded by a square bund.
|
This CIC will focus on inspection of bunds (and similar structures) around large immobile industrial storage tanks, typically found in tank farms, but also sometimes indoors (when conditions permit), and also around indoor reactors and pressure vessels. The CIC is also generally applicable to open collection systems used for mobile indoor and outdoor containers (drums, barrels and IBCs), consisting mainly of drip trays and small scale spill containment berms. See Text Box 1 for the terminology referring to specific types of collection systems covered by this document.
Not included in the scope are drainage and removal systems, including sumps and interceptors, in which spills are directed towards drains and trenches that are then connected to catch basins, carrying the liquid away from the process installation. Secondary containment systems for gaseous releases, such as the fluid curtains of specially designed gas tight buildings, are also out of scope.
|
 |
| |
Text Box 1 Explanation of terminology for secondary containment types covered by this document
Bunds, dykes and berms are used interchangeably for secondary containment around large, mainly outdoor storage tanks where flammable or toxic liquids are held. In this document, we will use the term “bunds”. For materials that are normally gases at ambient conditions, bunds are used where flash fractions are sufficiently low to merit them.
Earth berms and dykes. A berm around a large storage tank is a barrier that keeps liquids from escaping. It is a raised border separating different areas that may provide additional protection from flooding or erosion. Earth berms are constructed from various materials, including gravel, stone, soil, crushed rock, brick, or a combination of these materials.
Both bunds and berms should be designed to contain spillages and leaks of liquids used, stored or processed above ground and to facilitate clean-up operations.
Mobile collection systems prevent the spread of toxic or flammable substances to other plant areas, or to sumps and drains, where secondary effects resulting in a major accident could occur by domino effect. The systems are categorized as ‘mobile’ because they are not fixed in place, and can be moved around to accommodate plant layout changes, or the addition of containers that require the same kind of secondary protection. Drip trays are often used beneath equipment liable to small leaks, such as pumps, in process buildings and are effectively mini-bunds. Drip pallets and mobile spill containment berms are typically used for drums, barrels, and IBCs, in indoor or outdoor locations.
Mobile containment systems vary greatly in size and design. They are normally tailored to the individual item of equipment but may serve a number of items. They are often constructed of metals such as stainless steel or strong rigid plastics that can be readily moved. Drainage is not normally provided and liquid collected is normally removed using absorbent material, after neutralisation or dilution (if required).
The United Kingdom’s Health and Safety Executive page on Secondary Containment was an additional source for some of the information provided here. https://www.hse.gov.uk/comah/sragtech/techmeascontain.htm |
PURPOSE OF BUNDS
In general, bunds are provided for atmospheric storage tanks and for fully refrigerated storage tanks of liquefied gas, but not for pressure, or, with some exceptions semi-refrigerated storage of liquefied gas or for acid or alkali storage. Its containment function serves a number of purposes, including the following:
- prevent the flammable liquid or vapour from reaching ignition sources
- prevent the liquid entering the drainage or water systems where it may spread to uncontrolled ignition sources
- allow the controlled recovery or treatment of the spilled material
- minimise the surface area of the liquid and so reduce the size of any fire that may occur
- prevent the spread of burning liquids which could present a hazard to other plant or personnel both on and off site
- contain water used in firefighting or tank cooling
- prevent contamination of land and water courses
Therefore, the operator must convince the inspector with evidence that the design and maintenance of the bund system will support all these functions and that it will also function properly in an emergency.
ELEMENTS OF AN INSPECTION
The inspection of a bund, or any other open collection system, will generally focus on the following elements:
- Design
- Construction
- Maintenance and mechanical integrity
- Emergency response
DESIGN
Secondary containment should be designed in relation to the size and nature of the substance stored in the primary container. It should be big enough to contain the spilled substance, and the material of the secondary containment must be compatible with the substance.
Generally speaking, design of bunds around primary containment is fairly standardized, although which standards apply depends on what is being stored. The standards provide decision criteria that address a number of factors, in particular,
- the classification of the materials stored
- hazardous area classification,
- maximum capacity of the primary containment
- separation distances, if the bund surrounds a group of storage tanks,
- Hydrostatic and hydrodynamic loads on bund walls, and
- fire protection measures.
These factors will determine the size, capacity, dimensions, and composition of the bund. Decision criteria are given in various codes and other publications, such as NFPA 30[1] , API RP 752[2], HSG 176[3], and sometimes also national legislation.
The operator should be able to present documentation that indicates the design standards that were applied in construction of the bund.
If there has been a material change in the content of the primary containment, the operator should have documented a management of change (MOC) assessment of the adequacy of the bund to accommodate this change, and that changes to the bund design were subsequently implemented based on this assessment.
The bund wall should be designed to withstand a catastrophic tank failure and subsequent wave surge and overtopping event. The operator should be able to demonstrate that the tank is adequately resilient to such scenarios based on accident scenarios of the site.
Criteria influencing design of drip trays, drip pallets and spill containment bunds is described in Text Box 2.
| |
Text Box 2 Criteria for design of rip trays, drip pallets and spill containment bunds
Drip trays, drip pallets and spill containment bunds are simple trays or basins underneath storage containers to collect leaks and spills. They are intended for use with a single drum or a few small containers, in storage or at point of use. They are normally tailored to the individual item of equipment but may serve a number of items.
The size and capacity are determined on a similar basis as larger fixed open collection systems. For example, if you store oil on a drip tray in drums, the tray must be able to contain at least 25% of the total drum volume, or 110% of the largest one, whichever is the greatest.
Design should also take account of:
- the nature of the product that could be released, e.g. toxicity, persistence
- impermeability and resistance to attack from materials stored
- fixed fire-fighting systems and fire water containment
- fire resistance, including the effects of fire on the containment system
- effect of extremes in weather, freezing or high temperatures
- availability of ventilation at high and low levels (above secondary containment)
- the need to segregate products, especially if they are incompatible and would react if mixed
- separation from ignition sources, process areas, occupied buildings and site boundaries
- distance between other storage zones to stop fire spreading
- signage, to indicate the presence of secondary containment and any handling recommendations, for example, when equipment are being loaded or unloaded
Materials of construction are often metals such as stainless steel or strong rigid plastics that can be readily moved. Drainage is not normally provided and liquid collected is normally removed using absorbent material, after neutralisation or dilution (if required).
Drip trays can be used inside or outside buildings, but if used outside, regular procedures should include inspection following rainfall similar to bunds.
In general, the inspection and maintenance programmes for mobile and semi-mobile open spill collection systems should be modelled after those for bunds, with minor exceptions associated with their much smaller size.
The emergency response, fire prevention, and mitigation measures of the area in which they are located should also take into consideration the presence of localized secondary containment measures.
Services such as electricity supply should be carried over the secondary containment system rather than penetrating it. Mains water supply (except water-based fixed fire-fighting systems and safety shower/eye wash stations) shouldn’t enter the containment area of the store.
In clad buildings where racking extends above any containment system, provision should be made to prevent a high level leak running down between the cladding and the containment wall. Containers shouldn’t be stored at such a height or so close to the walls that they might fall outside the containment system or that liquid ‘jetting’ from a leak would reach over the wall.
Source: Guidance for Pollution Prevention Safe Storage of Drums and Intermediate Bulk Containers (IBCs): GPP 26) (Natural Resources Wales (NRW), the Northern Ireland, Environment Agency (NIEA) and the Scottish Environment Protection Agency (SEPA)).
|
CONSTRUCTION
Construction of the bund should also take into consideration appropriate requirements for materials of construction and for permeability based on design standards and local conditions.
Construction materials
The materials used in the bunding system should be able to withstand exposure to the hazardous material being stored and resist any corrosion or degradation that may occur over time. Compatibility should also be considered when selecting any sealants or coatings used in the construction of the bunding system.
Incompatible materials should not be stored in a common bund especially if the product material formed in the accidental mixing of the materials (e.g., due to error in tank filling) is incompatible with bund materials of construction.
In case of inflammable substance, the construction materials should be fire resistant. Particular attention should be paid to seams in the walls and seals around piping perforating the walls. Either a fire resistant material should be used, either the seams and seals should be protected against fire (e.g. by a non-combustible plate).
Permeability
It should be demonstrated that the bund beneath the tank floor is impermeable. Unlined earth bunds rely entirely on the impermeability of the soils forming the base and walls to provide containment.
Where pipework penetrates the bund wall and/or bund floor the operator must be able to demonstrate that the impermeability is not compromised.
On older sites, some bunds may have been built around existing tanks and may not have an impermeable layer beneath the tank floor. In such situations, the operator is required to have taken remedial actions, such as:
- retrospectively installing an impermeable bund floor
- installing a second floor within the tank with a drain out to the bund between the two tank floors. This system should be coupled with leak detection between the tank floors, in addition to leak detection under the original tank floor.
Drainage
The removal of rainwater is normally achieved by incorporating a drain at a low point of a sloping floor with a manual valve, normally kept closed. The capacity of the closed system should be based on documented estimates of maximum rain fall from historic data.
If the bund contains a rainwater drain, and requires manual draining, there must be a clear demonstration that the action can be done a safe manner in a bund fire event. Manually operated drain valves cannot be located inside bunds.
Where the design allows firewater to be drained off manually, there may be a risk of flame carryover through the drain system. This risk needs to be assessed and appropriate control measures should be put in place to prevent flame carryover.
There should be a means for removal of firewater from below the surface of the liquid, in particular, to evacuate a substance that is not miscible with water and has a lower density.
Leak detection equipment
Hydrocarbon detectors (flammable and/or toxic), positioned within the containment basins of the tanks, in order to promptly detect any product leaks.
Environmental impacts
The operator should have evaluated the site of the bund from a geological and a hydrogeological point of view. The analysis should consider environmental consequences of any accidental spills. It should also include an assessment of the time required for the pollutant to travel vertically and horizontally and to reach potentially sensitive targets. Depending on the impacts foreseen, the operator should have in place appropriate prevention and mitigation control measures.
Natural hazard events
The site should have conducted an assessment of risks from natural hazards, e.g., earthquakes and floods, and incorporated these into design criteria.
Many sites may not have conducted such evaluations before having constructed their bunds.
In this case, the operator must demonstrate that the bund has been retrofitted as necessary to address any risks from natural hazards not adequately mitigated by the original design.
In addition, bunds can protect the tank area from flooding, which may be taken into consideration in determining the dimensions (e.g., height, thickness).
Tertiary Containment
The operator should also calculate the possibility that the bund could overflow (‘bund overtop’) to determine whether a tertiary containment is required.
Some national authorities may require tertiary containment for certain specified dangerous substances.
The tertiary containment can be located in areas that are normally occupied by workers, such as yards. The location of the tertiary containment should be sited as to avoid risk to site personnel, responders or for escalation. In these situations, the emergency procedures must evaluate the additional risk of ignition of flammable vapours and health and safety risk to personnel), and establish control measures as necessary to mitigate the risk.
INSPECTION
A suitable bund inspection program is required to be in place set at appropriate intervals. Bunds should be immediately inspected after a tank loss of containment event. Bund impermeability should be confirmed by suitable tests such as a hydraulic water test in accordance with industry standards.
A typical inspection programme should consist of daily, weekly and monthly inspection protocols, as well as special protocols for checking the bund conditions following rainfall. In addition, bunds should be immediately inspected after a tank loss of containment event. Text Box 3 provides a list of some common signs of poor bund maintenance.
|
Text Box 3 Signs of badly maintained bund system
For a dike, berm, or other engineered secondary containment system:
- Capacity of the system to contain oil as determined in accordance with good engineering practice and the requirements of the rule
- Cracks in containment system materials (e.g., concrete, liners, coatings, earthen materials)
- Discoloration
- Presence of spilled or leaked material (standing liquid)
- Corrosion of the system
- Erosion of the system
- Operational status of drain valves or other drainage controls
- Dike or berm permeability
- Presence of debris;
- Level of precipitation in diked area and available capacity versus design capacity
- Location/status of pipes, inlets, and drainage around and beneath containers;
- Excessive vegetation that may inhibit visual inspection and assessment of berm integrity;
- Large-rooted plants (e.g., shrubs, cacti, trees) that could affect the berm integrity;
- Holes or penetrations to the containment system created by burrowing animals; and
- Drainage records for rainwater discharges from containment areas
Source: US EPA. SPCC Guidance for Regional Inspectors
|
MAINTENANCE
The maintenance of bunds should include a program of periodic integrity checks, through the use of non-destructive methods (NDT). Depending on the expected result, the test can be carried out visually or via instrumentation. Other elements may include:
- Where there are continuous monitoring systems, it is important that there are also periodic checks of the reliability of the instrumentation, based on the manufacturer's indications or on the operating experience.
- All bund repair work should be recorded in sufficient detail and the records kept for the duration of use of the bund.
- Operating schedules should include daily opening of the valve to remove accumulated water, this will also assist in identifying minor leaks.
EMERGENCY RESPONSE
Credible scenarios should be developed in consultation with the Fire and Rescue Services to inform the design of the containment system.
It is noted, however, that commonly available intumescent construction sealants are fire- rated for up to four hours. In the absence of any other information on the likely incident scenario, a minimum fire duration of four hours should be adopted.
The bund firewater retention capacity should be designed for the expected fire-fighting requirements based on the worst-case fire event. For example, a tank fire in a bund with multiple tanks would require fire water/foam application rates for the tank on fire and additional firewater application rates for adjacent tanks subject to flame impingement.
The use of adjacent bund retention capacity may be acceptable subject to a detailed risk assessment and appropriate design.
Where flammable materials are stored, the operator should
- have estimated the volume, of firefighting and cooling water that may have to be applied during an incident
- make sure that the components of the containment systems including the walls, and perhaps more importantly, the materials used to seal any joints, are fire resistant
- demonstrate that the firefighting water and foam demand requirements have been correctly specified for that bund.
For high-walled bunds, the site operator should demonstrate by means of a written risk assessment that there is not a risk of tanks floating in the event of the bund filling with firewater or due to extreme rainfall events.
The local emergency services, in particular the fire service, should be advised of the bund and firefighting equipment design & water usage in the event of a fire. Operators should have established the actions to be taken in case a bund risks flowing over, that should include:
- criteria for when to stop fire fighting attempts
- a strategy for emptying the bund, e.g., removal of content of bund to an additional containment (e.g., large trench), to relieve the danger and allow the firefighting to continue.
[1] NFPA 30, Flammable and Combustible Liquids CodeR
[2] API RP 752, Management of Hazards Associated with Location of Process Plant Permanent Buildings, Third Edition
[3] HSG 176 The storage of flammable liquids in tanks
REFERENCES
API Standard 650, 2013, Welded Tanks for Oil Storage
API Standard 653, Tank Inspection, Repair, Alteration, and Reconstruction
Natural Resources Wales (NRW), the Northern Ireland, Environment Agency (NIEA) and the Scottish Environment Protection Agency (SEPA), 2021, Safe Storage of Drums and Intermediate Bulk Containers, (IBCs): GPP 26, Version 1.2 https://www.netregs.org.uk/media/1885/guidance-for-pollution-prevention-26-2022-updated.pdf
United Kingdom Health and Safety Executive (UK HSE), (Online) COMAH Guidance, Technical Aspects, Measures Documents, Secondary Containment https://www.hse.gov.uk/comah/sragtech/techmeascontain.htm
United Kingdom Health and Safety Executive (UK HSE), 2015, HSG176, The storage of flammable liquids in tanks, UK HSE, 9780717666072 https://www.hse.gov.uk/pubns/books/hsg176.htm
U.S. EPA, 2013, Spill Prevention, Control, and Countermeasure (SPCC) Guidance for Regional Inspectors, Office of Emergency Management (5104A), EPA 550-B-13-001 https://www.epa.gov/sites/default/files/2014-04/documents/spcc_guidance_fulltext_2014.pdf
Walton, I. L. W., 2014, CIRIA Report C736, Containment systems for the prevention of pollution, CIRIA, ISBN: 978-0-86017-740-1 https://www.ciria.org/CIRIA/CIRIA/Item_Detail.aspx?iProductCode=C736F